HTPT Power Disk Steam Trap
- Size
- DN15~DN150
- Connection
- RF, NPT,SW
- Pressure
- PN10, PN16, PN25,PN40
- Materials
- Carbon Steel, Low temperature steel, Stainless steel.
Performance Advantages
Adopt chrominm=molybdenum-vanadium steel for its valve body.it is corrosion resistance,resistant to wear,heat resistance and longtime useful life.
Suitable for saturated vapour and over heating operation condition without and adjustment in the range of working pressure
Provided with inner Screen,and replace parts on pipeline easily.
Working Principle
With the different thermodynamic property caused by velocity of flow and volume from the steam and condensation water,the disk steam trap drive the hole of the switching valve and realize stopping steam and drain.
Application
Mainly used for high temperature and high pressure pipe and the operation condition whose saturated vapour pressure is 0.5-16MPa
Main basis for type selection
condesation water loading(discharge)kg/h(select the multiplying power 2-3 times)
Maximum working pressure MPa
Operation pressure differential MPa
Valve Material and nominal pressure
Connection mode and dimension
Use and Maintenance
Confirm the valve material pressure and check if the maximum is suitable for operation condition.
Before install,clean the pepeline and clear away sundries
The installation poisition shall be closed to heating equipment as much as possible.
Install the minimum point of pipe horizontally and the direction of flow should be the same to the lable of valve.
Install steam trap for each heating equipment in case cause influence each other.
under the safe operation of system,open the valve in front of the steam trap,make it rise up to normal station slowy.
Do time-based maintenance for the normal working of steam reap.
Get In Touch
We respect your privacy, Enquiry will send to our sales team, we will reply you with 12 hours.